Answer:
The short answer is yes, it is allowed by code. With that in mind I have only seen one project in a high-seismic region such as ours use joint reinforcement in place of bond beam construction and it did not comply with the code. So where does it say in the code that it is allowed and what should you look for?
IBC 2106.1 refers to Section 1.14.2.2 of ACI 530 for general reinforcing requirements for masonry shearwalls and further refers to Section 1.14.3 for Seismic Design Category (SDC) 'A', Section 1.14.4 for SDC 'B', Section 1.14.5 for SDC 'C', Section 1.14.6 for SDC 'D', and Section 1.14.7 for SDC 'E or F'. So what do these sections in ACI 530 state?
Section 1.14.2.2 of ACI 530 essentially states that horizontal reinforcement can be provided by either joint reinforcement at 16"o.c. or reinforced bond beams at 10'-0"o.c. This horizontal reinforcement must also be provided above and below all openings, at structurally connected roof and floor levels, and within 16-inches of the top of walls. If joint reinforcement is used it shall consist of at least at least two wires of W1.7 (9 gage). Ladder-type reinforcement as shown in Figure 1 below is most common.
Again, this section lists the general reinforcing requirements, but for this example I will assume the project falls within SDC 'D'. Per IBC 2106.1 it must therefore comply with the additional requirements of Section 1.14.6 of ACI 530. This section limits the spacing of horizontal reinforcement in masonry that is laid in a running bond pattern to 48"o.c., which is significantly tighter than the 10'-0" specified in Section 1.14.2.2. The maximum spacing is reduced to 24"o.c. for masonry laid in a stack bond pattern.
While most projects you review will meet the requirement, Section 1.14.6.3 also lists a minimum ratio of steel to masonry area of 0.0007. In the project I reviewed this is the item that did not meet code. On the project in question 9-gage ladder-type reinforcement was used at 8"o.c. in an 8" CMU wall. The joint reinforcement placed at 8"o.c. provided a steel area of 0.051in² per foot of wall. The cross sectional area per foot of 8” CMU walls is 91.5in² (7.625”x12”). Dividing the area of steel by the area of masonry gives a ratio of 0.00056, which is 20% less than the code-prescribed ratio of 0.0007. There are ways that joint reinforcement can be used in high-seismic regions and still meet the code requirements. In the example I used the engineer could have specified truss-type joint reinforcement (see Figure 2) or a thicker gage of ladder-type reinforcement. I hope that this helps.
Figure 1. Ladder-type
Figure 2. Truss-type

